BS EN 378 defines a safe concentration of HC’s as a practical limit (PL) The Practical Limit is approximately 20% of the lower flammability limit. For HC’s the PL is 0.008 Kg/m3. (8 g/m3).
Hydrocarbon-based refrigeration systems containing less than 150g can be placed in any location.
A Cold store 3.2m wide, 3.5m long and 2.5m high
The Practical Limit can also be used to determine the minimum room size a HC system can be installed in.
An HC system with a charge of 330g.
The Maximum charge for AC systems is determined by the floor area, the lower flammability limit and the height of the indoor unit.
M = 2.5 x LFL1.25 x h x √A